Skip to content

Softening & pretreatment

Water Hardness Levels: ppm, gpg and Softener Choice

HydroWorks Engineering Team 8 min read Updated

Quick answer

Hardness is the sum of calcium and magnesium, and the number only becomes useful when it is compared with the equipment it touches. This guide converts ppm, gpg and German degrees, sets out four practical hardness bands, and explains when a softener is justified for heaters, laundries, boilers and RO feed.

Bank of blue FRP softener vessels with brine tanks in a plant room
01

What is water hardness and how is it measured?

Hardness is the concentration of dissolved calcium and magnesium, expressed as an equivalent amount of calcium carbonate. The calculation is simple: multiply calcium in mg/L by 2.5 and magnesium in mg/L by 4.1, then add the two. A water with 80 mg/L calcium and 12 mg/L magnesium therefore has about 249 mg/L as CaCO₃. Other metals contribute in small amounts, but calcium and magnesium dominate in most supplies.

Field measurement usually uses an EDTA titration or a photometer. A titration kit gives a colour change at the endpoint and is accurate enough for routine checks; a photometer reads a coloured complex and is better for low hardness after softening. Test strips are acceptable for a first indication but not for sizing a softener, because a single colour block can cover 50 ppm or more.

Hardness unit conversions
UnitEquivalent as CaCO₃Example
mg/L (ppm)1 mg/L120 mg/L = 120 ppm
Grains per gallon (gpg)17.1 mg/L7 gpg = 120 mg/L
German degree (°dH)17.8 mg/L6.7 °dH = 120 mg/L
French degree (°f)10 mg/L12 °f = 120 mg/L

Conversions are rounded. Confirm the unit on the laboratory report before comparing it with a softener selection table.

02

What are the four hardness bands?

The industry uses four bands: soft, moderately hard, hard and very hard. They are conventions, not regulatory limits, and different countries draw the boundaries a little differently. The bands are still useful because they connect a laboratory number to a visible effect — scale on a heater, soap that will not lather, or a softener that regenerates every day.

A supply at 90 ppm is not a problem for a cold-water line, but it may be a problem for a combi oven with a small heat exchanger. Conversely, 140 ppm is manageable for a toilet supply and unacceptable for a boiler. Read the band together with the temperature, the equipment and the daily volume, not as a verdict on its own.

Hardness bands and typical effects
Bandmg/L as CaCO₃gpgTypical effect and response
Soft0–60<3.5Little scaling; softening optional and rarely economic
Moderately hard61–1203.5–7Decide by equipment, temperature and daily volume
Hard121–1807–10.5Softening usually recommended for heaters and RO
Very hard>180>10.5Softening required for boilers, laundry and RO feed

Bands are industry conventions. The decision also depends on alkalinity, pH, temperature and the equipment being protected.

03

Is hard water a health risk?

No. The WHO Guidelines for Drinking-water Quality do not set a health-based guideline value for hardness, and calcium and magnesium are essential nutrients at ordinary concentrations. Hard water is a nuisance and a cost, not a contaminant. The health question that does arise is sodium: softening exchanges calcium and magnesium for sodium, adding roughly 8 mg/L of sodium per grain per gallon of hardness removed.

For most people the added sodium is small. It matters when the source is very hard and the softened water is the only drinking supply, or when a strict low-sodium diet is medically required. In that case, treat the drinking-water line with RO, soften only the hot-water and appliance lines, or blend softened water with a low-hardness stream.

04

At what hardness should you install a softener?

Below 60 ppm, a softener is rarely economic. Above 120 ppm, softening is usually justified; above 180 ppm, it is normally necessary for heaters, boilers and RO feed. Between 60 and 120 ppm the answer depends on the equipment. A coffee machine, combi oven, steam iron or hot-water cylinder concentrates scale on its hottest surface and may need protection at 80 ppm, while a cold-water toilet line does not.

For reverse osmosis, the usual trigger is hardness above about 120 ppm as CaCO₃ when recovery above 65% is required, or when sulphate and silica are high. For boiler make-up, the target is near-zero hardness with controlled blowdown. For laundry, 0–60 ppm protects heaters and reduces detergent use. These are starting points; the local water analysis and equipment warranty decide the final specification.

Typical hardness targets by application
ApplicationTypical targetWhy
Drinking water80–150 mg/L as CaCO₃Taste and stability; hardness is not a health limit
Coffee and combi ovensBelow 60–80 mg/LSmall heat exchangers scale quickly
Laundry0–60 mg/LProtects heaters and reduces detergent
Boiler make-upNear zeroScale on heat transfer surfaces reduces efficiency
RO feedBelow 120 mg/L, or softenedControls calcium carbonate scaling at higher recovery

Typical values only. Confirm against the equipment manufacturer requirements and the local drinking-water standard.

05

How does hardness affect RO, boilers and laundry?

In an RO system, hardness salts concentrate in the brine as recovery rises. Calcium carbonate and magnesium salts can precipitate on the membrane surface, raising differential pressure and reducing permeate flow. Softening removes the hardness ions before they reach the membrane, which allows higher recovery and longer cleaning intervals. The trade-off is sodium: softening raises the sodium content of the feed but does not lower TDS, so the RO still does the desalination.

In a boiler, scale on a heat transfer surface acts as an insulator. Even a thin layer forces a higher flue-gas or tube temperature, wastes fuel and can overheat tubes. Softened make-up plus controlled blowdown is the standard defence. In a laundry, hardness consumes detergent, forms soap scum on linen and leaves grey, stiff fabric; 0–60 ppm is a common target for both linen quality and heater protection.

06

How should you test hardness correctly?

Sample at the point where the softener will be installed, not downstream of an existing softener or after a storage tank that may have blended water. Take the raw-water sample before any treatment, and repeat it in the wet and dry seasons if the source is a borehole, river or reservoir. For a softener check, sample the outlet weekly and record the result next to the salt added and the regeneration count.

Use a titration kit or photometer and report the result as mg/L CaCO₃, with the unit stated. A result of 7 gpg is not comparable with a 120 ppm selection table until it is converted to 120 mg/L. If the outlet hardness rises above about 1 ppm, check for a salt bridge, a blocked injector or a control valve set to the wrong resin volume before assuming the resin is exhausted.

07

Should you soften all the water or only part of it?

Softening every litre is rarely necessary. In a hotel, guest bathrooms, laundry and boiler make-up benefit, while irrigation, toilet flushing and cooling tower make-up may tolerate harder water. A partial-softening layout reduces salt consumption and the volume of brine discharge, and it keeps some hardness in the drinking-water supply, which many people prefer for taste.

Where the softener is the only treatment before a drinking-water point, confirm the sodium level against the local standard and the needs of the building occupants. Where an RO follows, softening only the RO feed is often the cleanest arrangement: the resin is protected, the salt use is limited to the process stream, and the rest of the building keeps its original water.

08

How do you choose between a softener, antiscalant and RO?

A softener removes hardness; an antiscalant keeps hardness salts dispersed so they do not crystallise on a membrane; RO removes the salts altogether. They are not interchangeable. Softening is the robust choice for boilers, laundries and high-recovery RO. Antiscalant suits low-to-moderate hardness and moderate recovery, where salt consumption and brine discharge are a concern. RO is justified when the water also needs desalination, not merely softening.

A practical decision sequence is: measure hardness and alkalinity; list the equipment to be protected; set the maximum allowable hardness at each point; then choose the lowest-cost process that meets those limits and can be maintained on site. The CK-SF series covers 0.5–15 m³/h, so most building-scale duties fall inside one catalogue range, but the model is still selected from peak flow, inlet hardness and regeneration hours.

Softener, antiscalant or RO — typical fit
SituationUsual choiceReason
Hardness above 180 ppm, boiler or laundrySoftenerRemoves hardness at the source; protects heat transfer
Hardness 60–120 ppm, moderate flowSoftener or antiscalantDecide by equipment sensitivity and salt cost
RO feed at 65% recovery or aboveSoftener or antiscalantPrevents calcium carbonate scaling on the membrane
Hardness plus high TDS or nitrateRO, with softening as pretreatmentOnly RO removes dissolved salts
Very hard water, drinking supply onlyRO for the drinking lineAvoids adding sodium to the drinking water

Typical guidance. Final selection depends on the full water analysis, recovery target and local discharge rules.

FAQ

Frequently asked questions

Questions buyers actually ask during sizing and quotation. Answers match the specifications above.

01 What hardness is considered hard water?
Above about 120 mg/L as CaCO₃, or 7 gpg, water is usually called hard. Above 180 mg/L (10.5 gpg) it is very hard. The bands are conventions: 120 ppm is the point where softening is usually worth considering, not a legal limit.
02 How do I convert gpg to ppm?
Multiply grains per gallon by 17.1. A reading of 10 gpg is about 171 mg/L as CaCO₃. For German degrees, multiply by 17.8; for French degrees, multiply by 10. Always state the unit when comparing a test result with a softener selection table.
03 Does a softener remove TDS?
No. A softener exchanges calcium and magnesium for sodium. TDS stays essentially unchanged and can rise slightly because sodium is lighter than the hardness ions it replaces. If TDS, nitrate or heavy metals must be reduced, use reverse osmosis.
04 Is softened water safe to drink?
Softened water is widely used for drinking and cooking. The main change is sodium, roughly 8 mg/L per gpg of hardness removed. For a very hard supply, that can matter to people on a strict low-sodium diet. If sodium is a concern, use RO for the drinking line or soften only the hot-water and appliance lines.
05 Why does hardness matter more in hot water?
Calcium carbonate is less soluble as temperature rises. The hottest surface in a heater or coffee machine therefore collects scale first, even when the cold-water hardness is moderate. That is why a 90 ppm supply can still damage a small heat exchanger while leaving a cold-water line clean.
06 Can I blend softened and raw water?
Yes, and it is common where some hardness is acceptable. A blending valve after the softener lets you target 80–150 ppm for drinking water or a lower value for process water. Confirm that the raw-water stream is potable and that the blend point cannot backflow into the softened line.
07 How often should hardness be tested?
Test the raw water monthly, or whenever the source changes, and test the softener outlet weekly. After a new installation or a resin change, test daily for the first week. Record the result with the salt added and the regeneration count so that a trend is visible before the outlet hardness fails.

Next step

Send your water analysis, get a factory quotation

Tell us the source water, TDS, hardness, iron and daily demand. Factory engineers reply with a flow rate, process train and budget range within one working day.